Post subject: RE: rozdiel v UPS
Posted: 15.05.2008 - 10:51 #64895
|
|
Majster
Joined: Feb 25, 2003
Posts: 2606
Location: BA,BB
|
|
Chalan wrote: ›bezudrzbovym auto baterkam sa nemusi dolievat nic predpokladam... je to tak? a bude to v strojovni pravdepodobne v plechovej skrini...
to som si tiez myslel kym mi nevyschol jeden clanok v bezudrzbovej baterke a kolegovi tiez ... a pritom to neboli "cinske" baterky z Tesca |
|
|
|
|
|
|
Post subject: RE: rozdiel v UPS
Posted: 15.05.2008 - 19:35 #64906
|
|
Ucen
Joined: Aug 28, 2006
Posts: 860
|
|
Tiez rozmyslam nad niecim podobnym. Mam 24V 120Ah bateriu.
Su to dva 12V clanky, takze sa da zapojit ako 12V 240Ah. Nabijaci prud ma vraj 36A :-DDD Takze dobijat by to z UPSky samozrejme neslo, raz za cas by sa dobila nabijackou manualne. UPSka by ju len nabijala defakto udrziavacim prudom
Hmm, na tom by sietove zariadenia, ci nejake mensie servre slapali hadam aj pol roka |
|
|
|
|
|
|
Post subject: RE: rozdiel v UPS
Posted: 15.05.2008 - 20:04 #64909
|
|
Majster
Joined: Máj 12, 2004
Posts: 4579
Location: Bratislava
|
|
eXplorer wrote: › Chalan wrote: ›bezudrzbovym auto baterkam sa nemusi dolievat nic predpokladam... je to tak? a bude to v strojovni pravdepodobne v plechovej skrini...
to som si tiez myslel kym mi nevyschol jeden clanok v bezudrzbovej baterke a kolegovi tiez ... a pritom to neboli "cinske" baterky z Tesca
pockaj to zartujes? co ste potom s tym robili? doliali? da sa to v bezudrzbovej baterke? |
|
|
|
|
|
|
Post subject: RE: rozdiel v UPS
Posted: 03.06.2008 - 16:43 #65748
|
|
Majster
Joined: Máj 12, 2004
Posts: 4579
Location: Bratislava
|
|
mam ups nova mg 600 avr so seriovym portom a chova sa divne...
zdroj bol zapnuty bez zataze niekolko dni, baterka sa teda dobijala a ostala na 83percent viac to proste neslo. tak som zapol PC s odberom 125W a odpojil upske stavu... baterka percentualne zacala klesat, kazdych 10sec cca o percento... zastavila sa po 7min pri 43percentach a ups vypla... podla mna dost malo na 600VA zdroj alebo sa mylim? ked som znova pustil stavu okamzite stupla bat zo 43percent na 78 a pomaly sa zacina nabijat... podla mna to nieje normalne chovanie UPSky... |
|
|
|
|
|
|
Post subject: RE: rozdiel v UPS
Posted: 04.06.2008 - 03:33 #65757
|
|
Majster
Joined: Okt 21, 2003
Posts: 4247
|
|
neviem ti, ale mali sme tu raz na teste UPSky Infosec, vydrzala tahat cca 5 minut bez ohladu na to, ci na tom bola zavesena kopa veci alebo skoro nic, zataz nemala vplyv na cas vypnutia. a korunou vsetkemu bolo to ze po obnoveni napajania bolo nutne tu UPSku manualne zapnut. infosec smart line, utekajte ludia. |
|
|
|
|
|
|
Post subject: RE: rozdiel v UPS
Posted: 04.06.2008 - 09:16 #65760
|
|
Majster
Joined: Máj 12, 2004
Posts: 4579
Location: Bratislava
|
|
druhy pokus po 3och hod nabijania, co je asi dost malo zo 43percent ukazovala 100percent, tak som jej znova vypol stavu, plynule klesala kapacita po percentach az sa to po 4och minutach zastavilo na 76percentach a vyplo sa to, ako je to MOZNE??? moze to robit zla baterka? alebo je proste vadna ta upska? |
|
|
|
|
|
|
Post subject: RE: rozdiel v UPS
Posted: 04.06.2008 - 20:04 #65772
|
|
Basic
Joined: Júl 12, 2003
Posts: 476
Location: nedaleko Turčianskych Teplíc
|
|
Povedal by som, ze vadne su tie percenta teda ten algoritmus ich vypoctu.. |
|
|
|
|
|
|
Post subject: RE: rozdiel v UPS
Posted: 04.06.2008 - 20:18 #65774
|
|
Basic
Joined: Júl 12, 2003
Posts: 476
Location: nedaleko Turčianskych Teplíc
|
|
Na to aby mohla UPS vediet kolko stavy v baterke este ma, musela by byt skalibrovana. Teda musela by cvicne prejst cely cyklus vybitia a nabitia a pri tom musi merat, kolko energie do baterky ulozila. Vtedy je schopa ukazovat nejake % akotak presne. Pokial nema tento algoritmus premakany a v nom riadne osetrene vsetky stavy, v ktorych sa UPSka pocas behu moze ocitnut, bude ukazovat bludy.
To iste je napriklad aj v notebookoch ukazovatel baterie. Niektore typy maju v biose moznost baterku skalibrovat. Ine co to premyslene nemaju hadzu cifry z brucha a zrazu sa stane, ze si bez stavy, aj ked si pred chvilou mal este 30%.
Vypnutie UPSky nastane pri poklese napatia baterky pod istu uroven. Napatie na nej klesa po urcitej charakteristike - krivke. Ta sa meni zivotnostou baterky. V istom bode moze krivka zacat prudko klesat a baterka dosiahne vypinacie napatie skor ako to software predpoklada, lebo on pocita na zaklade inej krivky.
Neviem ci ma chapete, ale mozno niekto nieco pochopil.. |
|
|
|
|
|
|
Post subject: RE: rozdiel v UPS
Posted: 05.06.2008 - 14:22 #65803
|
|
Majster
Joined: Máj 12, 2004
Posts: 4579
Location: Bratislava
|
|
ako teda vysvetlis ze 600VA zalozak s 7.2Ah baterkou utiahne 125W odber 4 max 7 min? stara baterka alebo lowendovy zalozak? podla prepoctu by to mal utiahnut 41min ratajme este nejake tie straty v menici a tiez tepelne straty, takze podla mna zdrava UPSka so 7.2Ah baterkou by mohla vydrzat tych 25-30min, mylim sa? |
|
|
|
|
|
|
Post subject: RE: rozdiel v UPS
Posted: 05.06.2008 - 14:48 #65805
|
|
Basic
Joined: Máj 15, 2008
Posts: 413
Location: Nedaleko od Losonca
|
|
Mam par MGE nova 600VA , stava im dochadza po nejakych 10 minutach alebo menej , zalohuju pccka z MK P4 3Ghz . |
|
|
|
|
|
|
Post subject: RE: rozdiel v UPS
Posted: 05.06.2008 - 15:44 #65807
|
|
Ucen
Joined: Apr 12, 2006
Posts: 930
Location: Vranov nad Topľou
|
|
Chalan wrote: ›ako teda vysvetlis ze 600VA zalozak s 7.2Ah baterkou utiahne 125W odber 4 max 7 min? stara baterka alebo lowendovy zalozak? podla prepoctu by to mal utiahnut 41min ratajme este nejake tie straty v menici a tiez tepelne straty, takze podla mna zdrava UPSka so 7.2Ah baterkou by mohla vydrzat tych 25-30min, mylim sa?
Jednoducho. Dajme tomu, ze ups je nastavena, aby sa vypla , ked prud klesne pod ( strelim cislo z brucha ) 0.5 A .
Kedze tvoja ups dosiahne tu krivku za 3 min, tak sa po troch minutach vypne aj ked, by este mala vydrzat dalsich 20 min, jednoducho, dosiahla pozadovanu hodnotu premennej. |
|
|
|
|
|
|
Post subject: RE: rozdiel v UPS
Posted: 05.06.2008 - 15:59 #65808
|
|
Ucen
Joined: Okt 21, 2004
Posts: 792
|
|
mala oprava
icerowicz wrote: ›
Jednoducho. Dajme tomu, ze ups je nastavena, aby sa vypla , ked napatie klesne pod ( strelim cislo z brucha ) 11,6 V .
|
|
|
|
|
|
|
Post subject: RE: rozdiel v UPS
Posted: 05.06.2008 - 21:49 #65811
|
|
Basic
Joined: Máj 31, 2006
Posts: 292
|
|
bakula wrote: ›mala oprava
icerowicz wrote: ›
Jednoducho. Dajme tomu, ze ups je nastavena, aby sa vypla , ked napatie klesne pod ( strelim cislo z brucha ) 11,6 V .
asi tak.
Okrem toho lowendy maju sami o sebe velku spotrebu, absolutne nevedia setrne zaobchadzat s baterkou. Velmi dobre sa mi osvedcili rackove apc a mge /vlastne teraz je to uz jedno/ napojene vo vetranom(klimatizovanom) racku na autobaterie Optima yellow top. Baterie mam dole v rackoch, kable vytiahnute k ups (8mm2 priemer). Ked k ups pripojite vacsiu kapacitu na aku je stavana, zvyknu sa nabijacie obvody prehrievat, preto je dobre ich mat odvetrane, pripadne klimatizovane prostredie je ideal. Jedine co neupravujem su unline ups, tie su myslim presne kalibrovane na kapacitu ktoru maju instalovanu. Nechovali sa mi dobre, pri akychkolvek upravach kapacity akumulatorov. |
|
|
|
|
|
|
Post subject: RE: rozdiel v UPS
Posted: 06.06.2008 - 16:45 #65824
|
|
Basic
Joined: Aug 17, 2007
Posts: 104
|
|
mam dotaz,
K tejto UPS http://eshop.bst.sk/?Mode=Sti&StiId=7381 som pripojil autobateriu(12V, 140AH) ale stale mi blika kontrolka pre vymenu baterie, pricom je uplne nabyta...
Vedel by mi niekto povedat ako by som to mal spravit?? |
|
|
|
|
|
|
Post subject: RE: rozdiel v UPS
Posted: 08.06.2008 - 18:44 #65859
|
|
Guru
Joined: Jan 24, 2004
Posts: 1685
|
|
qido wrote: › bakula wrote: ›mala oprava
icerowicz wrote: ›
Jednoducho. Dajme tomu, ze ups je nastavena, aby sa vypla , ked napatie klesne pod ( strelim cislo z brucha ) 11,6 V .
asi tak.
Okrem toho lowendy maju sami o sebe velku spotrebu, absolutne nevedia setrne zaobchadzat s baterkou. Velmi dobre sa mi osvedcili rackove apc a mge /vlastne teraz je to uz jedno/ napojene vo vetranom(klimatizovanom) racku na autobaterie Optima yellow top. Baterie mam dole v rackoch, kable vytiahnute k ups (8mm2 priemer). Ked k ups pripojite vacsiu kapacitu na aku je stavana, zvyknu sa nabijacie obvody prehrievat, preto je dobre ich mat odvetrane, pripadne klimatizovane prostredie je ideal. Jedine co neupravujem su unline ups, tie su myslim presne kalibrovane na kapacitu ktoru maju instalovanu. Nechovali sa mi dobre, pri akychkolvek upravach kapacity akumulatorov.
kolko ta vysla takato uprava ups-ka, baterie, respektive ake ma teraz toto nove UPS parametre? |
|
|
|
|
|
|